Version History of akYtec ALP

10.10.2023

2.4.335

New

  1. ST function blocks added:
    • It is possible to call an instance of a function and FB inside other FBs on ST:
        fb1 (In1 := Input, Q=> Out);
    • It is possible to access the inputs and outputs of an FB instance through a point:
        fb1.In1 := Input;
        fb1();
        Out := fb1.Out1;
    • Local one-dimensional arrays are supported

    The following devices support ST function blocks: PR100, PR102, PR200 and SMI200

Updates

Devices:

  1. PR200 Firmware v2.54:
    • Fixed problem with false triggering of outputs during firmware update
    • Fixed occasional problem with exiting the device system menu
    • Support for UTF-8 character encoding in visualization
    • Support for function blocks in ST language
    • Fixed error of negative measured resistance value when sensor breaks
  2. SMI200 Firmware v2.54:
    • Support for UTF-8 character encoding in visualization
    • Support for function blocks in ST language
  3. PR102 Firmware v2.54:
    • Fixed occasional incorrect operation of the device analog outputs
    • Increased stability of communication with PRM
    • Fixed false triggering of the device input when rebooting the controller
    • Fixed error in device cyclic reboot
    • Support for function blocks in ST language
  4. PR100 Firmware v3.08:
    • Internal work to optimize the operation of the device
  5. R100 [M02] Firmware v2.54:
    • Support for function blocks in ST language

Extension modules:

  1. PRM-x.1 Firmware v1.03:
    • Fixed incorrect operation of DO when updating the firmware
  2. PRM-x.3 Firmware v1.10:
    • Fixed incorrect operation of DO when updating the firmware
    • Fixed work with thermocouples
    • Increased stability of operation with PR102
  3. PRM-x.2 Firmware v1.01

Bug Fixes

  1. Error creating network variables of INT and REAL types with the same address on different RS485 ports
  2. Fixed detection of a "Conflict detected" error when creating two network variables of a slave device with the same addresses
  3. Fixed error "Not enough memory to allocate network variable"
  4. Error opening the project due to outdated properties of the FBD block. If a block contains an obsolete property, such as the Save State property of a CTU block, then the block property will be removed from the project
  5. The comment block on the workspace did not allow editing the variable
  6. Fixed bug when canceling macro password entry
  7. Changing the operating mode of the analog input (PR102 and PRM-x.2) despite the presence of communication with the input
  8. Improved the behavior of tooltips, which could appear late in the wrong place, overlapping other blocks while working in the workspace
  9. Fixed display of an error when network variable addresses intersect after sorting the variable table
  10. Fixed default values of read/write commands for network (master) variables of type INT/REAL when creating a variable in the PR200 visualization control "I/O box (INT/REAL)"
  11. Fixed the operation of the simulation of SHL and SHR operators in ST in ALP, which was different from the operation in the device
  12. Fixed the abbreviated name of the FB block "CLOCK WEEK" when copying/pasting into the workspace