New
-
"Switch Group" visualization element added for second-generation devices:
- Controls the value of a bound integer variable
-
When using Radio button type, only one option can be selected
-
When using Checkbox type, multiple options can be selected
-
"Switch" visualization element added for second-generation devices:
- Controls the value of a bound Boolean variable
-
Group polling support added for first-generation devices
-
Batch renaming of network variables added for first-generation devices in Master mode
-
Support for changing target devices between different product lines (within the same generation)
-
PID controller with auto-tuning added for second-generation devices (excluding PR103)
-
Incremental numbering implemented in parameter names when duplicating variables
-
Display added for system RAM, RAM, and visualization ROM usage indicators when usage is below 80%
-
Added buttons to create, delete, and duplicate directories in the variable table
-
Added "Usage in project" column for slave variables in the variable table
-
Added restriction on using the "[" and "]" characters in variable names
-
When opening old projects, all "[" and "]" characters in variable names will be automatically replaced with "{" and "}" respectively
-
Changed the display logic for the "Dynamic Text" element - lines are now displayed in the order defined in the control's
properties, rather than in ascending value order
Updates
-
PR103 – Firmware v1.11.2
- Fixed a rare issue causing incorrect values on DI and FDI inputs
-
PR205 – Firmware v1.10.1
-
Added support for PID controller with auto-tuning
-
Added support for "Switch" and "Switch Group" graphical controls
-
Fixed the visualization RAM calculation for several elements: Indicator, Switch, Circle/Sector, Button (with rounded corners and fully round)
Note: If previously created projects no longer fit within the visualization RAM limits, it is recommended to split the functionality of the most resource-intensive screens across multiple screens
Bug Fixes
-
Fixed an error when copying variables that contain parentheses in their names
-
Fixed focus loss on element after changing the target platform
-
Fixed an issue where ALP would close when deleting characters in the "int/float input/output" element
-
Fixed incorrect behavior of PR200 transistor output in PWM mode
-
Fixed an error when importing variable tables with empty parameter names
-
Fixed incorrect display of transistor output settings after switching the PR205 target platform
-
Fixed row sorting issues in the "Dynamic Text" element
-
Fixed a bug where PR102 logic was disabled during online debugging when switching between tabs